Diagnosis
16
Manual SD6
16.49 #<Placeholder>
16.50 *ParaModul ERROR:update firmware!
Resolution
Level
Response
A program run error was found in the
microprocessor.
Fault
The power stage is switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
The microprocessor is stopped and all device functions are inoperable.
Possible cause
Test
Measure
Confirmable
Error in code memory (bit dumped,
permanent).
Reestablish the operating conditions at the
time of the error and check whether the error
occurs again.
•
Reload the application in the drive
controller and save it.
•
Perform a firmware upgrade.
No
EMC error
Check the wiring for EMC-compliant design. Wire according to EMC regulations.
Triggering
Level
Response
The versions of configuration and firmware do not
match.
—
The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close. The brake chopper is
turned off.
Possible cause
Test
Measure
Confirmable
Old firmware version
—
Apply a suitable configuration or firmware.
No