Diagnosis
16
Manual SD6
16.10 40:Invalid data
Triggering
Level
Response
Counter
A data error was detected when initializing the
non-volatile memory.
Fault
The power board remains switched off and the drive is
torque-free/force-free. If the air override is inactive, a
possibly existing brake will be controlled to close.
Z40
Cause
Description
Measure
Confirmable
1:Error
Low level write/read error or timeout.
The drive controller must be sent in for
repair. Please contact our Service
department.
No
2:blockMiss
Unknown data block
3:dataSecurity
Block has no data security.
4:CheckSum
Block has a check sum error.
5:R/O
Block is r/o.
6:readErr
Start-up phase: Block read error
7:blockMiss
Block not found
8:Serial number
Serial number is incorrect/invalid.
32:el. nameplate
No nameplate data available
•
For STOBER standard motor: Please
contact our Service department.
•
For motor from other manufacturers: Set
B06
to
1:arbitrary setting
and manually
enter the motor data.
Yes
33:el.typeLim
Nameplate parameter cannot be entered
(limit value or existence).
•
Check the configuration of the drive
controller and motor.
•
Please contact our Service department.