Diagnosis
16
Manual SD6
16.7 37:Encoder
Triggering
Level
Response
Counter
Error due to encoder
Fault
The power board is switched off and the drive becomes
torque-free/force-free unless emergency braking
U30
(
A29
) is parameterized. If the air override is inactive, a
possibly existing brake will be controlled to close.
If the encoder is parameterized as a position encoder,
reference
I86
is deleted and the axis must be
rereferenced after the acknowledgement.
If the encoder is not connected when switching on the
control part power supply, the encoder supply is switched
off. Acknowledgement is then only possible by switching
the drive controller off and on.
Z37
Cause
Description
Measure
Confirmable
1:Para<>Encoder
Parameterization is not suitable for the
connected encoder.
Check the setting of the
H00
parameter.
Yes
2:maximum speed
B297
exceeded
•
Check the connection and shielding of
the encoder cable.
•
Reduce the electromagnetic
interference.
•
Check the parameterization of
B297
.
•
Please contact our Service department.
Yes
6:X4-EnDatfound
An EnDat encoder was detected at X4
although a different encoder was
parameterized.
Check the setting of the
H00
parameter.
Yes
7:AX6/IncEnc
A wire break in the A-channel was discover
on X4 with an incremental encoder.
Check the encoder cable of the incremental
encoder.
Yes