16.53 *ParaModul ERROR: ksb write error
16.54 *ConfigStartERROR parameters lost
Triggering
Level
Response
An error was detected when writing the
configuration in the configuration memory.
—
The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. If
there is a brake present it will be released automatically. The brake
chopper is turned off.
Possible cause
Test
Measure
Can be
acknowledge
d
Faulty flash memory.
—
Replace the Paramodule.
No
The configuration is too large for the
configuration memory.
•
Apply a suitable configuration via
DriveControlSuite and then save it
(
A00
).
•
Replace the Paramodule.
Triggering
Level
Response
No parameter values are saved in the
Paramodule.
—
The configuration does not start.
The power stage remains switched off, the drive is free of torque/force. A
possibly existing brake will be controlled to close The brake chopper is
turned off.
Possible cause
Test
Measure
Confirmable
The control part was switched off
while
A00
was active.
—
•
Apply a suitable configuration via
DriveControlSuite and then save it
(
A00
).
•
Replace the Paramodule.
No