16.13 43: AE1 wire break
Triggering
Level
Response
Counter
Wire break monitoring of analog input 1 in
operation mode
F116 = 2: 4 to 20mA
is reporting a
broken wire.
Fault
Parameterized fault response in
A29
:
•
A29 = 0:inactive
The power board is switched off and the drive
becomes torque-free/force-free. If the air override is
inactive, a possibly existing brake will be controlled to
close.
•
A29 = 1:active
The drive is stopped with a quick stop. If the air
override is inactive, a possibly existing brake will be
controlled to close at the end of the quick stop.
Z43
Possible cause
Test
Measure
Confirmable
There is a broken wire.
Check whether AE1+, AE1- and AE1 Shunt
are connected and whether the wiring is in
proper condition.
Connect the cables properly.
Yes