4.7.3.4. Ventilation Cooling
This function allows to open windows dependent on inside and outside temperature. This function is
normally used beyond working hours.
The outside temperature (3) must exceed before the function is activated.
Windows will be opened, if inside temperature (4) and the set delta between inside and outside temper-
ature (5) is exceeded. Windows will be closed, if outside temperature (3), inside temperature (4) or the
set delta between inside and outside temperature (5) is below.
This function is only carried out if no other function with a higher priority is active.
The corresponding KNX objects are KNX.MC.Zone_Energy_Saving_Bit_OUT[n] and
KNX.MC.Zone_Position_UP_DOWN_1Byte_OUT[n], whereby “n” stands for the respective selected
zone 1-16.
Parameter:
1. Select Ventilation Cooling.
2. Enable/disable function.
3. Outside temperature threshold
the necessary measured temperature which must be exceeded or
be below to activate or deactivate the function.
4. Inside temperature threshold
the necessary measured temperature which must be exceeded or
be below to activate or deactivate the function.
5. Outside/inside temperature threshold
the necessary measured temperature delta which must be
exceeded or be below to activate or deactivate the function.
6. Inside temperature threshold
the necessary measured temperature which must be exceeded or
be below to activate or deactivate the function.
7. Outside/inside temperature threshold
the necessary measured temperature delta which must be
exceeded or be below to activate or deactivate the function.
8. Position, to which is moved to with activating the function.