6.1. Object overview
A maximum of 183 communication objects are available. The number of the objects is dependent on
the number of the zones.
6.1.1. List of Objects
No.
Object name
Model Description
1
KNX.MC.Info_Azimuth_1Byte_OUT
1 Byte The object sends telegrams with the value
of the sun azimuth.
2
KNX.MC.Info_Date_3Byte_IN_OUT
3 Byte The object sends or receives telegram
with the date.
3
KNX.MC.Info_Elevation_1Byte_OUT
1 Byte The object sends telegrams with the value
of the elevation of the sun.
4
KNX.MC.Info_Out_Temp_2Byte_OUT
2 Byte The object sends telegrams with the value
of the outside temperature.
5
KNX.MC.Info_Rain_Bit_OUT
1 Bit
The object sends “1” if the rain sensor on
the Outside Sensor Box recognizes rain
and sends “0” when the rain has stopped.
6
KNX.MC.Info_SensorFailure_Bit_OUT
1 Bit
The object sends “1” if an error occurred
and sends “0” when the error has
stopped.
7
KNX.MC.Info_Sun_Lux_2Byte_OUT[1]
2 Byte The objects send telegrams with the value
of the sun‘s brightness of the respective
sun sensor.
8
KNX.MC.Info_Sun_Lux_2Byte_OUT[2]
9
KNX.MC.Info_Sun_Lux_2Byte_OUT[3]
10
KNX.MC.Info_Sun_Lux_2Byte_OUT[4]
11
KNX.MC.Info_Sun_Lux_2Byte_OUT[5]
12
KNX.MC.Info_Sun_Lux_2Byte_OUT[6]
13
KNX.MC.Info_Sun_Lux_2Byte_OUT[7]
14
KNX.MC.Info_Sun_Lux_2Byte_OUT[8]
15
KNX.MC.Info_Time_3Byte_IN_OUT
3 Byte The object sends or receives telegram
with the time.
16
KNX.MC.Info_Version_2Byte_OUT
2 Byte The object sends telegrams with the soft-
ware Version the KNX Master Control.
17
KNX.MC.Info_Wind_Dir_1Byte_OUT
1 Byte The object sends telegrams with the value
of the wind direction.