Explanation of the functions:
1. Display whether zone is in automatic or manual mode
2. Assigned zone name
3. Installed end product of the zone
4. Safety functions
a. Alarm input: The function becomes active when over the object KNX
KNX.MC.Zone_Major_Alarm_Bit_IN [n] “1” is transmitted. Then all end products go to the upper
end position (0 %). Chapter 6.1.1 KNX Object no. 88ff).
b. Everything locked at 0 %: The function is triggered when in the KNX Operating Software indi-
vidual zones or the whole building are locked. Then all end products go to the upper end posi-
tion (0 %) (chapter 4.6.2).
c. Error: When activated, all end products go to the 0 % position. For the identification of error see
chapter 4.8.2 and error code.
d. Wind speed: The wind alarm is triggered with the exceeding of the defined threshold value.
Then all end products in a zone go to the safety position (chapter 4.7.1.1).
e. Wind direction: The wind direction alarm is triggered if the wind speed lies above the threshold
value and the wind comes from the defined direction. Then all end products in a zone go to the
safety position (chapter 4.7.1.2).
f. Snow: The snow alarm is triggered at temperatures under 4° C and the measurement by rain is
triggered. Then all end products in a zone go to the safety position (chapter 4.7.1.8).