c. Shift time interval:
With pressed mouse button on the time interval (2) to be shifted, click and
drag this in the desired direction. Release the mouse button. The set time is indicated on the
right beside the bar.
d. Delete time interval:
With pressed mouse button on one of the bar ends of the time interval to be
deleted (2), click and drag this until it disappears. With the button “delete” (3), all time intervals
can be deleted.
2. Inverts the time interval.
3. Position to which is moved after colour change white to green in the time line (1).
4. Angle to which is moved after colour change white to green in the time line (1). Not available with all
end products.
5. Description with explanation.
6. “Clear” to delete all set time intervals in this zone.
7. “OK” for taking on the setting.
8. “Cancel” for quitting without settings.
4.7.1.10. Reset Control To Automatic
This function enables the possibility to change the priority automatic function and priority manual func-
tion on a KNX actor (e.g. ref.1860114 animeo KNX 4 AC Motor Controller WM) by using the KNX object.
Up to three time points can be defined at which this takes place automatically. You can also do this
manually in the software by pressing “Reset“.
The corresponding KNX object is KNX.MC.Zone_Timer_Reset_To_Auto_Bit_OUT[n] whereby “n”
stands for the respective selected zone 1-16.
Parameter:
1. Select reset control to automatic.
2. Enable/disable function „Reset control to automatic“.
3. “Reset“, to return to automatic manually. After activating Reset, the following KNX objects are sent
to the KNX Bus.
a. KNX.MC.Zone_Timer_Reset_To_Auto_Bit_OUT
“1”
b. KNX.MC.Zone_Security_Low_Prio_Bit_OUT
“0”
c. KNX.MC.Zone_Security_High_Prio_Bit_OUT
“0”
d. KNX.MC.Zone_Position_UP_DOWN_1Byte_OUT
“0-255”, the current calculated position.
e. KNX.MC.Zone_Slat_Position_1Byte_OUT
“0-255”, the current calculated angle. Not available
in all end products.
4. Enable/disable time 1-3.
5. Enable/disable to send the current position and angle of the end product.
a. KNX.MC.Zone_Position_UP_DOWN_1Byte_OUT
“0-255”, the current calculated position.
b. KNX.MC.Zone_Slat_Position_1Byte_OUT
“0-255”, the current calculated angle. Not in all
end products available.