-91-
No. JXC
※
-OMT0002-C
Name of the
controller
setting
software
(code)
G
roup
How to
deactivate
Alarms and countermeasures
Speed
exceeded set
value (1-144)
D
RESET
and
SVON is
ON
< Details >
The motor speed has exceeded the specified value, possibly due to an
external force, etc.
<Countermeasure>
Make improvements to ensure that the motor speed will not exceed the
maximum speed of the actuator.
Caution
Please refer to the actuator manual or the catalogue for the maximum
speed of the actuator.
Actuator power
supply voltage
is outside set
range. (1-145)
D
RESET
and SVON
is ON
< Details >
The motor power supply voltage is detected in the controller to be outside
of the specified range. The controller will check the lower limit of the motor
power supply voltage only when the servo is ON.
<Countermeasure>
Check the voltage supplied to the controller motor power supply (M24V).
Caution
If the power supply is a type with “inrushcurrent protection”, a voltage
drop may cause an alarm during acceleration/ deceleration.
< Details >
The alarm may be caused by regenerative power depending on the
method of operation of the actuator.
<Countermeasure>
Check if the operating condition of the actuator is within the specification
range.
Caution
Please refer to the actuator manual or the catalogue for the method of
operation of the actuator.
Controller
temperature
exceeded set
range. (1-146)
D
RESET
and SVON
is ON
< Details >
The temperature around the power element of the controller is too high.
<Countermeasure>
Make improvements so that the temperature around the controller is kept
appropriate.