AXP1440-C07 Operations
AXP1440-C07 Installation and Use (6806800V18A)
91
Power is introduced to the PEM using a DC power cable attached to the terminal blocks on
the front of the module (power input cable and return cable). The terminal block consists of
a dual stud connection which prevents the power cables from rotating and provides secure
contacts for the cable lug. There is a plastic cover that protects the cable connections.
4.5.2
IPMC Circuitry
Each PEM is capable of monitoring voltage and circuit breaker status. The PEMs are
loaded with the AdvancedTCA IPMC firmware. Preprogrammed FRU and Sensor Data
Record (SDR) information reside on the PEM and is accessible from the SAM1620-D
through the IPMB ports of the PEM. In addition, the IPMC monitoring functions include
digital inputs to detect circuit breaker trips, voltage sensors to detect backplane voltages,
current sensors to detect current to the backplane, and on-board circuitry to detect failures
on the PEM. The PEMs are managed by the Sentry Shelf Management software. Refer to
the
Centellis 4440/4620 Control via IPMI Programmer’s Reference
guide listed in
for more information.
provides a conceptual view of the connections between the PEMs,
backplane, FTMs, and SAMs.
NOTICE
The DC power inputs must only be attached to approved Telephone Network
Voltage (TNV) or Safety Extra Low Voltage (SELV) branch circuits. Branch circuits
must comply with all requirements called for in these safety standards: IEC 60950,
EN 60950, CAN/CSA-C22.2 No. 60950. Attaching inputs to non-TNV/SELV approved
power sources will cause the system to fail compliance with safety regulations.
Table 4-1
PEM IPMB Addresses
Description
IPMB Address
PEM A
0x66
PEM B
0x68
Summary of Contents for 6806800V18A
Page 1: ...AXP1440 C07 Installation and Use P N 6806800V18A February 2020...
Page 8: ...6 AXP1440 C07 Installation and Use 68068000V18A Table of Contents...
Page 10: ...List of Figures 8 AXP1440 C07 Installation and Use 68068000V18A...
Page 12: ...List of Tables 10 AXP1440 C07 Installation and Use 68068000V18A...
Page 40: ...38 AXP1440 C07 Installation and Use 6806800V18A Notice de S curit Notice de S curit...
Page 52: ...50 AXP1440 C07 Installation and Use 6806800V18A Sicherheitshinweise Sicherheitshinweise...
Page 90: ...88 AXP1440 C07 Installation and Use 6806800V18A Site Preparation Site Preparation...
Page 163: ...1...