102
AXP1440-C07 Installation and Use (6806800V18A)
AXP1440-C07 Shelf Installation
AXP1440-C07 Shelf Installation
5.7
DC Power Cable
Power is introduced to the shelf through redundant DC PEMs. The recommended power
cable is an 4 AWG gauge that meets the specifications for this shelf. There are four lugs for
each PEM. Two are straight and the other two are custom offset lugs. The end that
connects to the external DC power source should be equipped with an 8mm terminal.
NOTICE
Always check with your local building authorities for wire sizing requirements for
your environment.
The installation must comply with the 1993 National Electric Code (NEC) and other
applicable codes.
The DC power inputs must only be attached to approved Telephone Network
Voltage (TNV) or SELV (Safety Extra Low Voltage) branch circuits. Branch circuits
must comply with all requirements called for in these safety standards: IEC 60950,
EN 60950, CAN/CSA-C22.2 No. 60950. Attaching inputs to non-TNV/SELV approved
power sources will cause the system to fail compliance with safety regulations.
The ground wire must be connected to a reliable earth ground connection to comply
with Class 1 Equipment requirements.
Multiple power sources are present.
Service only by qualified service personnel.
Mehrfache Energiequellen.
Handhabung nur durch geschultes Personal.
Des sources multiples de pouvoir sont présentes.
L'entretien de cet équipement doit être effectué par du personnel de service qualifié.
Table 5-2
Power and Ground Wire Signals
Wire
Signal
Earth Ground
PE GND (Primary Earth Ground)
Input power
-48VDC/-60VDC nominal
Return
-48VDC RETURN
Summary of Contents for 6806800V18A
Page 1: ...AXP1440 C07 Installation and Use P N 6806800V18A February 2020...
Page 8: ...6 AXP1440 C07 Installation and Use 68068000V18A Table of Contents...
Page 10: ...List of Figures 8 AXP1440 C07 Installation and Use 68068000V18A...
Page 12: ...List of Tables 10 AXP1440 C07 Installation and Use 68068000V18A...
Page 40: ...38 AXP1440 C07 Installation and Use 6806800V18A Notice de S curit Notice de S curit...
Page 52: ...50 AXP1440 C07 Installation and Use 6806800V18A Sicherheitshinweise Sicherheitshinweise...
Page 90: ...88 AXP1440 C07 Installation and Use 6806800V18A Site Preparation Site Preparation...
Page 163: ...1...