Safety Notes
AXP1440-C07 Installation and Use (6806800V18A)
23
This equipment shall be located in the same immediate area (such as adjacent
cabinets) as any other equipment that has a connection between the earthed
conductor of the same DC supply circuit and the earthing conductor, and also the
point of earthing of the DC system. The DC system shall not be earthed elsewhere.
The DC supply source shall be located within the same premises as this
equipment.
Make sure you have an earth ground connection that is free of any disconnecting
device, such as a power switch or fuse, between the DC source and the earth
ground connector. A disconnecting device could result in the ground being
disconnected and the potential of injury from electrical shock.
System Overheating
If you set the fan speed manually through the shelf manager, constantly monitor the system
temperature to prevent overheating.
Make sure that the environmental and power requirements are met while operating the
system.
Injuries or Short Circuits - Blade or Power Supply
If the ORing diodes of the blade fail, the blade may trigger a short circuit between input line
A and input line B so that line A remains powered even if it is disconnected from the power
supply circuit (and vice versa).
To avoid damage or personal injury, always check that no hazardous voltage is present
before servicing equipment.
Expansion
System Overload
To avoid an overload of the system, check the total power consumption of all components
installed. Make sure that the individual output current of any source stays within its
acceptable limits (see the technical specification of the respective source or component).
Loss of Safety Compliance - Using Additional Plug-in Blades
The system may become noncompliant by the addition of plug-in cards. Regulatory
compliance is the responsibility of the system integrator.
Summary of Contents for 6806800V18A
Page 1: ...AXP1440 C07 Installation and Use P N 6806800V18A February 2020...
Page 8: ...6 AXP1440 C07 Installation and Use 68068000V18A Table of Contents...
Page 10: ...List of Figures 8 AXP1440 C07 Installation and Use 68068000V18A...
Page 12: ...List of Tables 10 AXP1440 C07 Installation and Use 68068000V18A...
Page 40: ...38 AXP1440 C07 Installation and Use 6806800V18A Notice de S curit Notice de S curit...
Page 52: ...50 AXP1440 C07 Installation and Use 6806800V18A Sicherheitshinweise Sicherheitshinweise...
Page 90: ...88 AXP1440 C07 Installation and Use 6806800V18A Site Preparation Site Preparation...
Page 163: ...1...