Safety Notes
AXP1440-C07 Installation and Use (6806800V18A)
19
Installation codes: This unit shall be installed in accordance with the National
Electrical Code, Articles 110.16, 110.17, and 110.18 and the Canadian Electrical
Code, Section 12.a
Overcurrent protection: A readily accessible listed branch circuit overcurrent
protective device must be incorporated into the building wiring. For appropriate
AWG rating of the overcurrent protection device, see NEC Table 310.16 and other
national regulations.
The protective bonding conductor depends on your power distribution topology.
Make sure that you use an appropriate protective bonding conductor regarding the
rating of the branch circuit protection.
Install the system safely. Make sure that cables and cords are out of the way.
Make sure that the set-up is comfortable for users.
System Damage
WARNING: The intra-building port (s) of the equipment or subassembly is suitable for
connection to intra-building or unexposed wiring or cabling only. The intra-building port (s)
of the equipment or subassembly MUST NOT be metalically connected to interfaces that
connect to the outside plant (OSP) or its wiring. These interfaces are designed for use as
intra-building interfaces only and require isolation from the exposed OSP cabling. The
addition of primary protectors is not sufficient protection in order to connect these interfaces
metalically to OSP wiring.
System Damage
Environmental contamination can impair system operation.
Locate the system in a stable area free of excess movement and jarring and free of dust,
smoke, and electrostatic discharge (ESD).
Make sure that the temperature does not exceed the operating temperature given in the
environmental requirements in this manual and allow room for proper air flow for cooling.
Personal Injury or System Damage
The system is supplied by a TNV2 voltage. This voltage is considered hazardous. Make
sure that the power supply meets the local safety standards.
System Overheating
Improper cooling leads to blade damage.
To ensure proper cooling always operate the system in a horizontal position. Keep clear at
least 2.36 inches (6cm) of clear space adjacent to the cooling vents on the chassis front
and back side.
Summary of Contents for 6806800V18A
Page 1: ...AXP1440 C07 Installation and Use P N 6806800V18A February 2020...
Page 8: ...6 AXP1440 C07 Installation and Use 68068000V18A Table of Contents...
Page 10: ...List of Figures 8 AXP1440 C07 Installation and Use 68068000V18A...
Page 12: ...List of Tables 10 AXP1440 C07 Installation and Use 68068000V18A...
Page 40: ...38 AXP1440 C07 Installation and Use 6806800V18A Notice de S curit Notice de S curit...
Page 52: ...50 AXP1440 C07 Installation and Use 6806800V18A Sicherheitshinweise Sicherheitshinweise...
Page 90: ...88 AXP1440 C07 Installation and Use 6806800V18A Site Preparation Site Preparation...
Page 163: ...1...