Site Preparation
AXP1440-C07 Installation and Use (6806800V18A)
83
To guarantee proper blade operation, make sure that the temperatures at the locations
specified in the following table are not exceeded. If not stated otherwise, the temperatures
should be measured by placing a sensor exactly at the given locations.
3.2.3.2
Power Requirements
Make sure that a suitable -48VDC power source is within reach of the shelf. Two PEMs can
be installed in the shelf. The shelf may require up to 125A DC through two 80A feeds. The
required cable size for 80A is 4 AWG wire.
Table 3-2
Critical Temperature Limits
Component
Temperature Limit
Air inlet (shelf front)
+55°C (131°F)
Air outlet (shelf rear)
+70°C (158°F)
Power entry module lug-plastic washer
+70°C (158°F)
>+70°C (158°F) and m90°C (194 °F): the
cables must be isolated and must be approved to be
used in this temperature range.
>+70°C (158°F) and m90° (194°F): the
service personnel may touch the components: the
cables must be isolated and the hot surface icon
must be attached. The cables must be approved to
be used in this temperature range.
Table 3-3
System Power Requirements
Feature
Value
Rated voltage input current
-48VDC (SELV)
-60VDC to -72VDC (TNV-2)
80A (X2)
Operating voltage range
-40 to -72VDC
Personal or System Damage
The shelf may be supplied by a TNV-2 voltage. This voltage is considered hazardous.
Make sure that the power supply unit meets the local safety standards.
Summary of Contents for 6806800V18A
Page 1: ...AXP1440 C07 Installation and Use P N 6806800V18A February 2020...
Page 8: ...6 AXP1440 C07 Installation and Use 68068000V18A Table of Contents...
Page 10: ...List of Figures 8 AXP1440 C07 Installation and Use 68068000V18A...
Page 12: ...List of Tables 10 AXP1440 C07 Installation and Use 68068000V18A...
Page 40: ...38 AXP1440 C07 Installation and Use 6806800V18A Notice de S curit Notice de S curit...
Page 52: ...50 AXP1440 C07 Installation and Use 6806800V18A Sicherheitshinweise Sicherheitshinweise...
Page 90: ...88 AXP1440 C07 Installation and Use 6806800V18A Site Preparation Site Preparation...
Page 163: ...1...