Extended metering functions
The metering function
PLUS
is used to implement extended protective functions beyond the functionality of the trip units.
1)
ANSI definition:
Ratio of the largest difference between the phases and the average of all 3 phases.
If one of these parameters exceeds or falls below its default settings, the trip unit is tripped after the adjusted delay via the
c
.
The parameters can be adjusted via:
- the test socket with the BDA
- the PROFIBUS-DP
- the MODBUS
- the graphical display (ETU776)
Parameter
Range
Delay
Undervoltage
100 - 1100 V
0 - 15 sec.
Overvoltage
200 - 1200 V
0 - 15 sec.
Active power in normal direction
1 - 12000 kW
0 - 15 sec.
Active power in reverse direction
1 - 12000 kW
0 - 15 sec.
Overfrequency
40 - 70 Hz
0 - 15 sec.
Underfrequency
40 - 70 Hz
0 - 15 sec.
Phase current unbalance
1)
5 - 50%
0 - 15 sec.
Phase voltage unbalance
1)
5 - 50%
0 - 15 sec.
Phase rotation
Pickup THD current
3 - 50%
5 - 15 sec.
Pickup THD voltage
3 - 50%
5 - 15 sec.
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......