Recommendation for supporting the main conductors
X
The connecting bars of all poles should be braced together, line and load side separately.
Frame size
Rated breaking current
(kA)
Dimension x
(mm)
(inch)
II
50 / 65
250
10
85
200
8
100
200
8
II fused
200
200
8
III
85 /100
200
8
130 / 150
100
4
III fused
200
200
8
These distances are recommendations and are not construction specifications. All designs should be type tested according to
ANSI C37.20.1 and ANSI C37.51 for design validation.