18 – 9
18.2
Truck Operated Contacts - TOC (Cradle Accessory)
The cradle can be retrofitted with truck-operated contacts (TOC). These optional accessories allow the customer to evaluate the position of
the circuit breaker in the cradle.
(1)
TOC signaling switch module
Three versions are available (Order numbers
WLGSGSW111 (Version 1):
- One form C contact for DISCONNECT position (S30)
- One form C contact for TEST position (S31)
- One form C contact for CONNECT position (S34)
WLGSGSW321 (Version 2):
- One form C contact for DISCONNECT position (S30)
- Two form C contacts for TEST position (S31 and S32)
- Three form C contacts for CONNECT position (S33, S34, and S35)
WLGSGSW6 (Version 3):
- Six form C contacts for CONNECT position (S30, S31, S32, S33, S34, and S35)
Terminals
The TOC accessory is equipped with an integrated terminal block. The integrated terminal block is of spring clamp design, and will accept
1xAWG 20 – 1xAWG 14 for each point
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
(1)
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......