9 – 78
9.2.3
External Cublicle
BUS
modules
9.2.3.1 General
Application
External
c
modules are used for communication between the WL circuit breaker and the secondary equipment in the circuit
breaker panel. They are provided to control analog indications, transmit the circuit breaker tripping status and the reason for tripping
and to read additional control signals. Furthermore, with one of these modules it is possible to implement a zone selective interlocking for
short-circuit protection.
(1)
Indicator LED
(2)
Rotary coding switch
(3)
Connection X3:
c
(4)
Connection X5: inputs or outputs
(5)
Connection X4: inputs or outputs
(6)
Connection X2:
c
(7)
Connection X1:
c
(8)
"TEST" button
Installation
The external
c
modules are snapped onto a standard 35-mm DIN rail inside the switchgear panel. It must be ensured that the
length of the connecting cable of the first module to the circuit breaker does not exceed 6.5 ft.
Connection setup
The
c
modules must only be connected to each other and to the circuit breaker using the pre-assembled cables supplied.
These cables are also used for the 24 V DC voltage supply of the
c
modules.
If more than two
c
modules are connected, the 24 V DC voltage supply must be fed via a separate cable from module to module.
Only one
c
module can be connected directly to a circuit breaker. Further modules must be connected from module to module.
Radial cables are not permissible.
If provided, the ZSI module is always the first module, and must be connected directly to the circuit breaker.
The
c
cable must be connected to the X3 connection of the last module with a 120
0.5 W resistor.
The total length of the
c
cables must not exceed 30 ft from auxiliary current plug X8 of the circuit breaker to the last
c
module.
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......