23 – 11
23.6
Replacing the circuit breaker internal
contact assemblies
If the circuit breaker's internal contacts need to be replaced following an inspection, this can be done using the following procedure.
When replacing the circuit breaker's internal contacts, it is recommended that all three poles be replaced at the same time. It is also required
that the arc chutes be replaced when the breaker internal contacts be replaced at the same time. See
Checking arc chutes (page 23-5)
for
replacement arc chutes.
-
OPEN the circuit breaker and discharge the closing spring
-
Remove the circuit breaker from the cradle
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
WARNING
High speed moving parts.
Can cause serious personal injury.
Discharge the closing spring before inspection and before carrying out any work on the circuit breaker.
NOTE
Pole assemblies are not field-replaceable for frame size III, M-class circuit breakers.
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......