9 – 64
MODBUS Functionality
Transmission Protocol
The COM16 module operates in the RTU transmission mode. ASCII transmission mode is not supported.
Overview of supported Functions
The COM16 module provides the following MODBUS function codes for accessing the data contained in the WL circuit breaker.
FC
Name
Description
02:
Read Discrete Inputs
Reads the state of the Bits in the Status Register
01:
Read Coils
Reads the state of multiple Control Bits and Extra Flags
05:
Write Single Coil
Sets the state of a single Control Bit or Extra Flag
15:
Write Multiple Coils
Sets the state of multiple Control Bits and Extra Flags
04:
Read Input Registers
Reads the Basic Data Registers. Three Basic Types (1, 2 and 3) are supported.
03:
Read Holding Registers
Reads a complete data set.
16:
Write Multiple Registers
Writes a complete data set.
07:
Read Exception Status
Reads the state of eight Exception Status bits
08:
Diagnostics
Function provides a method for checking the communication between the master
and the slave
11:
Get Comm Event Counter
Returns a status word and an event count from the communications event counter
12:
Get Comm Event Log
Returns a status word, event count, message count, and a field of event bytes
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......