19 – 8
19.2
Installing interlocking module
-
- Switch off and discharge the closing spring
- Remove the breaker from the cradle
or remove the fixed-mounted breaker if necessary
- Remove front panel and side cover on the right, if required
19.2.1
Installing intermediate shaft and coupling
Fitting
WARNING
High speed moving parts.
Can cause serious personal injury.
Discharge the closing spring before inspection and before carrying out any work on the circuit breaker.
Frame size
Length L (mm)
I
48
II
118
III
232
Mechanical interlooking module
with ring
1