Indicators and operating elements
There are additional indicators and operating elements available for field installation.
14.1
Limiting Access to OPEN/CLOSE Buttons
This accessory kit allows the access to the OPEN and CLOSE buttons of the circuit breaker to be limited in any combination of the supplied
components.
- OPEN the circuit breaker and discharge the closing spring
- Move the circuit breaker into the withdrawn position in the cradle
- Remove front panel
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
WARNING
High speed moving parts.
Can cause serious personal injury.
Discharge the closing spring before inspection and before carrying out any work on the circuit breaker.