24 – 9
WL Circuit Break er
F unction ov er vie w of the electronic tr ip units
Basic functions
ETU748
ETU776
Long-time ov ercurrent pro tection
F unction can be switched ON/OFF
–
–
Se tting range
I R = I n x …
0.4, 0.45, 0.5, 0.55,
40-100% of In (Adjustable in Amps )
0.6, 0.65, 0.7, 0.8,
0.9, 1
Switch-selectable ov erload p rot ection
(
I 2 t or I 4 t dependent function)
Se tting range of delay time clas s
t R at I
2 t
(seconds)
2, 3.5, 5.5, 8, 10,
2 … 30 (step: 0.1s)
14, 17, 21, 25, 30
Se tting range of delay time
t R at I
4 t
(seconds)
1, 2, 3, 4, 5
1 … 5 (step: 0.1s)
Thermal memor y
(via slide switch)
(on/off via key pad
or communications)
Phase los s sensitivity
at
t sd =20ms (M)
(on/off via key pad
or communications)
N-conductor pro tection
–
F unction can be switched ON/OFF
(via slide switch)
(via key pad or communications)
N-conduct or se tting range
I N = I n x …
0.5 … 2, OFF
Shor t-time dela y ed ov ercurrent pro t ection
F unction can be switched ON/OF F
–
(via key pad or communications)
Se tting range
I sd = I n x …
1.25, 1.5, 2, 2.5,
1.25 … 0.8 x I
cw = max
3, 4, 6, 8, 10, 12
(step: 10A)
Se tting range of delay time
t sd , f ix ed
(seconds)
M, 0.1, 0.2, 0.3, 0.4
M, 0.08 … 0.4, OFF (step: 0.001s)
Switch-selectable sho rt -t ime dela y
shor t-cir cuit p rot ection
(
I 2 t dependent function)
(via rot ar y coding switch)
(via key pad or communications)
Se tting range of time dela y
t sd at I
2 t
(seconds)
0.1, 0.2, 0.3, 0.4
0.1 … 0.4 (step: 0.001s)
Zone Selectiv e Int erlocking (ZSI) function
per CubicleBUS module
per CubicleBUS module
Instantaneous ov ercurrent pro tection
F unction can be switched ON/OFF ,
Ext ended Instantaneous P rot ection
is enabled when OFF
–
(via key pad or communications)
Se tting range
I i = I n x …
–
I
i
=
I
cw
= EIP
1.5 x
I
n
… 0.8 x
I
cs
= max, OFF=
I
cw
=EIP
Ground-fault pro tection
O
(field installable module)
O
(field installable module)
Tr ip and alarm function
(via key pad or communications)
De t ection of the ground fault curr ent
by r esidual summing me thod
De t ection of the ground fault curr ent
by dir ect summing me thod
Se tting range of the
I g f or trip
A, B, C, D, E
A … E (step: 1A)
Se tting range of the
I g f or alarm
A, B, C, D, E
A … E (step: 1A)
Se tting range of the delay time
t g
(seconds)
0.1, 0.2, 0.3, 0.4, 0.5
0.1 … 0.5 (step: 0.001s)
Switch-selectable
ground fault p rot ection
(
I 2 t / fix ed)
Se tting range delay time
t g at I
2 t
0.1, 0.2, 0.3, 0.4, 0.5
0.1 … 0.5 (step: 0.001s)
ZSI ground function
per CubicleBUS module
per CubicleBUS module
available
–
not available
O
optional
L
N
S
I
G
Extended Instantaneous Protection (EIP) allows the WL circuit breaker to be applied at the withstand rating of
the circuit breaker with minus 0% tolerance; this means there is no instantaneous override at all. EIP further
enables the circuit breaker to be applied up to the full instantaneous rating of the circuit breaker in systems
where the available fault current exceeds the withstand rating.
Ground Fault Module cannot be removed after installation.
2
Note: ETU776 settings via WLBDA, Modbus, or Profibus: 1A steps
Via ETU Keypad: Below 1000A: 10A steps 1000A-1600A: 50A steps
1600A-10000A: 100A steps Above 10000A, 1000A steps
1
3
Notes:
M
= Motor protection setting indicates phase loss sensitivity is enabled. LT pick-up reduced 80% when phase unbalance > 50%. ST = 20 ms
Communications
= Setting the parameters of the trip unit via the Breaker Data Adapter, MODBUS, or PROFIBUS
Key pad
= Direct input
the trip unit
I n
3
2
2
1
ed
-
on
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......