12 – 12
12.8.2.4 Wiring the Contact Blocks
The contact blocks are designated (front of cradle to rear of cradle) S50, S51, S52, and S53. Each contact block contains one “a” and one
“b” contact, with the terminal designations as shown below. Each terminal accepts a maximum of one wire, 14 AWG (or smaller), and shall
be tightened to 7 lbin (0.8 Nm).
12.8.2.5 Installing the Contact Blocks
The contact blocks must be firmly seated, with the feet of the contact block latched into the MOC assembly housing. If there is damage to
the contact block assembly, a replacement contact block must be used. Replacement contact blocks may be purchased per catalog number
WLMOCSWK (includes four replacement contact block assemblies).
NOTICE
MOC Reliability
May cause intermittent signaling.
All four contact blocks, whether wired or not, must be installed into the MOC assembly to ensure reliable operation.
NOTICE
Contact block damage.
May cause loss of signaling.
Do not over-extend the feet of the contact block when reinstalling into the MOC assembly.
7 mm
1/4“
S50
S51
S52
S53
a
3
4
b
1
2
a
3
4
b
1
2
a
3
4
b
1
2
a
3
4
b
1
2
Attention: Four
contact
blocks must be installed
for proper operation
Attention: Four
contact
blocks must be installed
for proper operation
3,0 x 0,6
1/8“
0,8 Nm
7 lb-in
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......