8 – 7
8.8
Trip unit circuitry for ETU745-776
8.8.1
With Breaker Status Sensor (BSS)
and metering module
1)
Terminating resistor 120
0.5 W on X8-1 / X8-2, if no external
c
module
2)
If
no
metering module and
no
BSS module is used:
Direct connection X8 to ETU
- BSS module: Breaker Status Sensor
-
c
: Bus system for interconnection of circuit breaker components and connection to the fieldbus:
PROFIBUS-DP with COM15
MODBUS with COM16
- ETU: Trip Unit
- S40 signaling switch
"
ready-to-close
"
- S41 signaling switch for spring charge level
- S43 signaling switch 2nd shunt trip F3 or F4
- S44 signaling switch for main contacts OPEN / CLOSE position
- S45 Bell Alarm signaling switch