9 – 69
Basic Data Types
Basic data types 1, 2 and 3 are supported. Basic data type 1 is the default setting. Basic data type 1 consists of 7 registers,
basic data type 2 consists of 13 registers and Basic data type 3 consists of 22 registers.
Basic data is accessed using the function:
04 Read Input Registers - Reads the Basic Data including the Status Register
Basic Data Type 1 Registers and Default Data Points
Register
Byte
Name
Default Data Point – WL
1
0, 1
Status Register
WL status bits
2
2, 3
Data Block 1
Phase L1 current
3
4, 5
Data Block 2
Phase L2 current
4
6, 7
Data Block 3
Phase L3 current
5
8, 9
Data Block 4
Current in phase under highest load
6 LOW
10
Block 1 property byte
Property byte of phase L1 current
6 HIGH
11
Block 2 property byte
Property byte of phase L2 current
7 LOW
12
Block 3 property byte
Property byte of phase L3 current
7 HIGH
13
Block 4 property byte
Property byte of max current in phase under highest load
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......