9 – 66
Changing the communication parameters
The communication parameters of the COM16 module can be changed by writing the required parameters (baud rate, serial configuration
and MODBUS communication address) in data set 160.
Register
Dataset 160 – communication parameters
Address: A000 hex, Registers: 39, Access: Read / Write
Address
High/
Low
dec
hex
Description
Data
point
Source
WL
Source
VL
1
Source
VL
2
Format
Length
(Bit)
Scaling
40961
0xA001
-
Header; value 0x00 00 00 00
-
COM16
COM11
COM21
-
32
-
40963
0xA003
LOW
Reserved
-
-
-
-
-
8
-
40963
0xA003
HIGH
MODBUS address
5
COM16
COM11
COM21
unsign
ed char
8
0
40964
0xA004
LOW
Basic type of MODBUS data
transfer
6
COM16
COM11
COM21
Hex
2
-
40964
0xA004
HIGH
Reserved
-
-
-
-
-
8
-
40965
0xA005
-
Data in the cyclic profile of
MODBUS
7
COM16
COM11
COM21
Format
(7)
224
-
40979
0xA013
-
Reserved
-
-
-
-
-
48
-
40982
0xA016
-
IP address of the BDA/BDA
PLUS
10
BDA
-
-
Format
(10)
40
-
40985
0xA019
LOW
MODBUS transmission rate
(baud rate)
427
COM16
COM11
COM21
Format
(427)
8
-
40985
0xA019
HIGH
Parity
428
COM16
COM11
COM21
Format
(428)
8
-
40986
0xA01A
-
Reserved
-
-
-
-
-
144
-
40995
0xA023
LOW
Property byte (parity)
428
COM16
COM11
COM21
PB
8
-
40995
0xA023
HIGH
Property byte (MODBUS
transmission rate (baud
rate))
427
COM16
COM11
COM21
PB
8
-
40996
0xA024
LOW
Reserved
-
-
-
-
PB
8
-
40996
0xA024
HIGH
Property byte (MODBUS
address)
5
COM16
COM11
COM21
PB
8
-
40997
0xA025
LOW
Property byte (basic type of
MODBUS data transfer)
6
COM16
COM11
COM21
PB
8
-
40997
0xA025
HIGH
Reserved
-
-
-
-
PB
8
-
40998
0xA026
LOW
Property byte (data in the
cyclic profile of MODBUS)
7
COM16
COM11
COM21
PB
8
-
40998
0xA026
HIGH
Reserved
-
-
-
-
PB
8
-
40999
0xA027
LOW
Property byte (IP address of
the BDA/BDA
PLUS
)
-
BDA
-
-
PB
8
-
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......