19 – 1
19
Mechanical circuit breaker interlocking
Mechanical interlocking module
(1)
Cradle
(2)
Fixed-mounted breaker
19.1
Configurations
A maximum of three circuit breakers may be interlocked.
NOTE
For proper function of the interlocking device, the following minimum prerequisites have to be met:
1
Bowden cables are to be laid out as straight and as unbowed as possible.
2
Bending radii of the Bowden cables must exceed > 20" (500 mm).
3
The total curvature of the Bowden cable must not exceed 540 degrees.
4
When stacking interlocked circuit breakers vertically, the interlocking devices shall be vertically aligned with each other.
5
Circuit breakers intended to be interlocked must be positioned so that Bowden cables of 6 ft or 15 ft (2 m or 4.5 m) length can
be laid out per the above requirements 1-4.
6
Before adjusting the interlocking device, the Bowden cables must be secured, e.g. using cable ties.
7
Adequate spacing is required to provide enough room for adjustment of the interlocking device.
(2)
(1)
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......