9 – 51
9.1.11
Internal trip unit self-test on
the overcurrent tripping function
For commissioning and function testing.
Conditions
- Trip unit is activated by:
operating current
external 24 V DC voltage supply
- Current not in overload range
Internal circuit breaker self-test without tripping
Normal operation of the circuit breaker is not impaired
1
2
Running light
All indicators will light up one after other (from left to right or from top to bottom)
3
The flashing time corresponds to the long-time delay
t
R
The flashing time deviates more than
10%
from the set long-time
delay
t
R
4
The L-tripping indicator lights up
Test
OK
T.U. ERROR indicator lights up
Test
not OK
Test
not OK
Trip unit is defective, even if the L-tripping indicator lights up
5
- LED goes out after 30 sec.
- End of internal self-test
- Premature ending of test by
pressing CLEAR
6
Trip unit OK
Testing with handheld test device
Handheld test device (page 9-97)
The test can be canceled
at any time by pressing CLEAR
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......