9 – 81
Setting principle
Indicators
Module test
The correct operation of the
c
modules can be verified in the test mode. The test mode is started by pushing the "TEST" button
once. All outputs and the associated LEDs are switched off. The color of the DEVICE LED changes from green to yellow.
Testing inputs and outputs
Pushing the "TEST" button several times in quick succession when an LED is on switches the respective input/output on and off alternately.
LED
Indication
Significance
DEVICE
green
Module in operation
yellow
Module in test mode
red
Module faulty
c
green
Connection to
c
available
off
No connection to
c
All other LEDs
yellow
Option set or signal available
off
Option not set or no signal available
NOTICE
Unintended operation of the circuit breaker and other devices.
The test circuits of this unit emit real output signals that may cause operation of the circuit breaker and other devices that
may be connected to the associated
c
module.
During the test, the circuit breaker and downstream devices shoud be isolated to prevent unintended device operations.
Pressing the
"
TEST
"
Button
Reaction
Twice quickly
- LED 1 on
- Input/output 1 on
After a pause,
twice quickly
- LED 1 and input/output 1 off, LED 2 on
- Input/output 2 on
After a pause,
twice quickly
- LED 2 and input/output 2 off, LED 3 on
- Input/output 3 on
...
...
After a pause,
twice quickly
- LED 5 and input/output 5 off, LED 6 on
- Input/output 6 on
After a pause, once
Input/output 6 off, all LEDs on
Once
Test mode starts again, all inputs/outputs and the associated LEDs are off
The value 0.1 is set if the
rotary coding switch is positioned
3 x 0.5
1/8“
in this
segment
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......