10 – 3
10.3
Field Installation of a reclosing lockout
To activate the Bell Alarm lockout, the automatic reset must be removed. The tripping solenoid, the tripped indicator and the tripped signal
must be reset manually at the breaker. Reclosing of the circuit breaker is blocked until the trip indicator has been reset.
- OPEN the circuit breaker and discharge the closing spring
- Move the circuit breaker into the withdrawn position in the cradle
- Remove front panel
.
- Remove the trip unit
.
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
WARNING
High speed moving parts.
Can cause serious personal injury.
Discharge the closing spring before inspection and before carrying out any work on the circuit breaker.
Summary of Contents for UL 1066
Page 56: ...7 5 7 2 Frame size II fused ...
Page 58: ...7 7 ...
Page 63: ...7 12 8 27 210 0 8 27 210 0 8 27 210 0 3 75 95 2 ...
Page 64: ...7 13 ...
Page 65: ...7 14 7 7 Frame size III fuse carriage ...
Page 66: ...7 15 ...
Page 69: ...7 18 7 9 External sensor for neutral conductor WLNCT2 ...
Page 70: ...7 19 WLNCT3 ...
Page 85: ...9 5 I tripping Ground fault tripping ...
Page 231: ...15 12 Pre assembling the locking module Installing 0767 1 2 3 4 6 5 ...
Page 232: ...15 13 1 Socket head cap screw M5 with washer and nut 7 8 Size 4 5 Nm 45 lb in ...
Page 289: ...23 7 23 3 3 Installing arc chutes 1 2 6 5 PH 2 0043 02 3 4 5 6 For frame size III 3 PH 2 ...
Page 298: ...23 16 6 7 8 9 5 2 1 Size 5 mm ...
Page 333: ......