6 – 2
6.1.2
Positions of the circuit breaker in the cradle
(4)
Secondary circuit
(5)
Primary circuit
(6)
Cubicle door
(7)
Shutter
Diagram
Positon indicator
Primary
Circuit
Secondary
Circuit
Cubicle Door
Shutter
Withdrawn
position
disconnected
disconnected
open
closed
Disconnected
position
disconnected
disconnected
closed
closed
Test position
disconnected
connected
closed
closed
Connected
position
connected
connected
closed
open
(1)
(2)
(4)
green
(3)
green
blue
red