3. Perform the following in HW Config:
– Connect the drive unit to PROFIBUS and assign the address.
– Set the telegram type.
The same telegram type as on the slave should be set for every drive object exchanging
process data via PROFIBUS.
The master can send more process data than the slave uses. A telegram with a larger
PZD number than is assigned for the drive object STARTER can be configured on the
master.
The PZDs not supplied by the drive object are filled with zeros.
The setting "without PZD" can be defined on a node or object (e.g. infeed controlled via
terminals).
4. Assign the I/O addresses according to the user program.
Diagnostics options
The standard slave diagnostics can be read online in the HW config.
SIMATIC HMI addressing
You can use a SIMATIC HMI as a PROFIBUS master (master class 2) to access SINAMICS
directly. With respect to SIMATIC HMI, SINAMICS behaves like a SIMATIC S7. For accessing
drive parameters, the following applies:
● Parameter number = data block number
● Parameter sub-index = bit 0 ... 9 of data block offset
● Drive object number = bit 10 ... 15 of data block offset
Pro Tool and WinCC flexible
The SIMATIC HMI can be configured flexibly with "Pro Tool" or "WinCC flexible".
The following specific settings for drives must be observed when configuration is carried out
with Pro Tool or WinCC flexible.
Controllers: Protocol always "SIMATIC S7 - 300/400"
Table A-7
Additional parameters
Field
Value
Network parameter profile
DP
Network parameter baud rate
Any
Communication partner address
PROFIBUS address of the drive unit
Communication partner
slot/rack
Don’t care, 0
Communication
A.1 Communication