A.1.5.5
Supported objects
Overview
Object class
Object name
Objects
required
SINAMICS
objects
hex
dec
1 hex
1
Identity object
x
‑
4 hex
4
Assembly Object
x
‑
6 hex
6
Connection Management Object
x
‑
32C hex
812
Siemens Drive Object
‑
x
32D hex
813
Siemens Motor Data Object
‑
x
F5 hex
245
TCP/IP Interface Object
1)
x
‑
F6 hex
246
Ethernet Link Object
1)
x
‑
300 hex
768
Stack Diagnostic Object
‑
x
302 hex
770
Adapter Diagnostic Object
‑
x
303 hex
771
Explicit Messages Diagnostic Object
‑
x
304 hex
772
Explicit Message Diagnostic List Object
‑
x
401 hex
1025
Parameter object
‑
x
402 hex ...
43E hex
1026...10
86
Parameter object
‑
x
1)
These objects are part of the Ethernet/IP system management.
For Assembly Object "4 hex" you define the data length. Assembly Object is assigned a cycle
in the control system.
Identity Object, Instance Number: 1 hex
Supported services
Class
● Get Attribute all
● Get Attribute single
Instance ● Get Attribute all
● Get Attribute single
● Reset
Table A-32
Class Attribute
No.
Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Communication
A.1 Communication
Industrial Security
192
Configuration Manual, 08/2017, A5E36912609A