5. Create an additional setpoint slot 6 for the first drive object using the "Insert slot" button
behind the existing setpoint slot 5.
Figure A-14 Insert new slot
6. Under the "PROFIBUS Partner" column, change the new setpoint slot 6 from an "output"
type to a "slave-to-slave communication" type.
7. In the first column, select the PROFIBUS DP address of the publisher, in this example "5".
All PROFIBUS DP slaves are listed here, for which actual value data can be retrieved. It
also provides the possibility of sharing data via slave-to-slave communication within the
same drive device.
Communication
A.1 Communication
Industrial Security
Configuration Manual, 08/2017, A5E36912609A
131