Set dynamic braking
Parameter Description
p0219
Braking power of the braking resistor (factory setting: 0 kW)
For p0219 > 0, the inverter deactivates the VDC_max controller.
For vector control, p0219 defines the regenerative power limit p1531.
3
PD[
3
W
S
Using p0219, you define the maximum braking power that the braking resistor must ab‐
sorb.
For an excessively low braking power, the inverter extends the motor ramp-down time.
The SIZER PC tool supports you when calculating the braking power.
Configuring support (Page 461)
p2106
BI: External fault 1
p2106 = 722.x
Signal for monitoring the braking resistor overtemperature with digital
input x of the inverter.
Monitoring the temperature of the braking resistor (Page 113)
An application example for configuring a drive with braking resistor is provided in the Internet:
Engineering and commissioning series lifting equipment/cranes (
support.industry.siemens.com/cs/de/en/view/103156155
)
Advanced commissioning
6.20 Electrically braking the motor
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF