Procedure
Proceed as follows to select the motor standard and system of units using STARTER:
1. Select in the "Configuration" project tree.
2. Select under the "Units" tab.
3. Select the system of units.
4. Select the technological unit of the technology controller.
5. Select the motor standard.
6. Save your settings.
7. Go online.
The inverter signals that offline, other units and process variables are set than in the inverter
itself.
8. Accept these settings in the inverter.
You have selected the motor standard and system of units using STARTER.
Advanced commissioning
6.14 Selecting physical units
SINAMICS G120C converter
214
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF