Bit Meaning
Explanation
Signal inter‐
connection in
the inverter
1
0 = OFF2
Switch off the motor immediately, the motor then
coasts down to a standstill.
p0844[0] =
r2090.1
1 = No OFF2
The motor can be switched on (ON command).
2
0 = Quick stop (OFF3)
Quick stop: The motor brakes with the OFF3 ramp-
down time p1135 down to standstill.
p0848[0] =
r2090.2
1 = No quick stop (OFF3) The motor can be switched on (ON command).
3
0 = Inhibit operation
Immediately switch-off motor (cancel pulses).
p0852[0] =
r2090.3
1 = Enable operation
Switch-on motor (pulses can be enabled).
4
0 = Disable RFG
The inverter immediately sets its ramp-function gener‐
ator output to 0.
p1140[0] =
r2090.4
1 = Do not disable RFG The ramp-function generator can be enabled.
5
0 = Stop RFG
The output of the ramp-function generator stops at the
actual value.
p1141[0] =
r2090.5
1 = Enable RFG
The output of the ramp-function generator follows the
setpoint.
6
0 = Inhibit setpoint
The inverter brakes the motor with the ramp-down time
p1121 of the ramp-function generator.
p1142[0] =
r2090.6
1 = Enable setpoint
Motor accelerates with the ramp-up time p1120 to the
setpoint.
7
0 → 1 = Acknowledge
faults
Acknowledge fault. If the ON command is still active,
the inverter switches to the "switch-on inhibit" state.
p2103[0] =
r2090.7
8, 9 Reserved
10 0 = No control via PLC
Inverter ignores the process data from the fieldbus.
p0854[0] =
r2090.10
1 = Control via PLC
Control via fieldbus, inverter accepts the process data
from the fieldbus.
11 1 = Direction reversal
Invert setpoint in the inverter.
p1113[0] =
r2090.11
12 Reserved
13 1 = MOP up
Increase the setpoint saved in the motorized potenti‐
ometer.
p1035[0] =
r2090.13
14 1 = MOP down
Reduce the setpoint saved in the motorized potenti‐
ometer.
p1036[0] =
r2090.14
15 Reserved
Status word 1 (ZSW1)
Bit Meaning
Remarks
Signal inter‐
connection in
the inverter
0
1 = Ready for switching on
Power supply switched on; electronics initialized;
pulses locked.
p2080[0] =
r0899.0
1
1 = Ready
Motor is switched on (ON/OFF1 = 1), no fault is
active. With the command "Enable operation"
(STW1.3), the inverter switches on the motor.
p2080[1] =
r0899.1
Advanced commissioning
6.6 Drive control via Modbus RTU
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
195