5.5.5
Select the application class
Starting quick commissioning
Procedure
Proceed as follows to start the quick commissioning:
When selecting an application class, the inverter assigns the motor control with the appropriate
default settings:
● [1]
Standard Drive Control (Page 143)
● [2]
Dynamic Drive Control (Page 144)
● [0] Expert - or if no application class is listed:
Select the suitable application class
When selecting an application class, the inverter assigns the appropriate settings to the motor
control.
Application class
Standard Drive Control
Dynamic Drive Control
Motors that can be
operated
Induction motors
Induction and synchronous motors
Application exam‐
ples
● Pumps, fans, and compressors with flow
characteristic
● Wet or dry blasting technology
● Mills, mixers, kneaders, crushers, agitators
● Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
● Basic spindles
● Pumps and compressors with displacement
machines
● Rotary furnaces
● Extruder
● Centrifuges
Commissioning
5.5 Quick commissioning with a PC
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
141