Exception: a mechanical coupling ensures that all of the motors always operate with the same
speed.
Table 6-56
Advanced settings
Parameter Description
p0346
Motor excitation build up time
Wait time between switching on the motor and enabling the ramp-function generator.
p0347
Motor de-excitation time
Within the motor de-excitation time, after an OFF command, the inverter prevents the
induction motor from being switched on again.
p1201
Flying restart enable signal source (factory setting: 1)
Defines a control command, e.g. a digital input, which enables the flying restart function.
p1202
Flying restart search current (Factory setting depends on the Power Module)
Defines the search current with respect to the magnetizing current (r0331), which flows
in the motor during the flying restart.
p1203
Flying restart search current factor (Factory setting depends on the Power Module)
The value influences the speed with which the output frequency is changed during the
flying restart. A higher value results in a longer search time.
If the inverter does not find the motor, reduce the search speed (increase p1203).
Advanced commissioning
6.26 Flying restart – switching on while the motor is running
SINAMICS G120C converter
304