Table 10-6
Frame size B, 3-phase 380 … 480 VAC, +10%, -20%
Article No. without filter
Article No. with filter
6SL3210-1KE21-3U . 1
6SL3210-1KE21-3A . 1
6SL3210- 1KE21-7U . 1
6SL3210-1KE21-7A . 1
Rated/LO base load power
5.5 kW
7.5 kW
Rated/LO base load input current
16.5 A
21.5 A
Rated/LO base load output current
12.5 A
16.5 A
HO base load power
4.0 kW
5.5 kW
HO base load input current
12.8 A
18.2 A
HO base load output current
8.8 A
12.5 A
Power loss with filter
177 W
244 W
Power loss without filter
174 W
240 W
Required cooling air flow
9 l/s
9 l/s
Weight with filter
2.5 kg
2.5 kg
Weight without filter
2.3 kg
2.3 kg
Table 10-7
Frame size C, 3-phase 380 … 480 VAC, +10%, -20%
Article No. without filter
Article No. with filter
6SL3210-1KE22-6U . 1
6SL3210-1KE22-6A . 1
6SL3210-1KE23-2U . 1
6SL3210-1KE23-2A . 1
6SL3210-1KE23-8U . 1
6SL3210-1KE23-8A . 1
Rated/LO base load power
11 kW
15 kW
18.5 kW
Rated/LO base load input current
33.0 A
40.6 A
48.2 A
Rated/LO base load output current
25 A
31 A
37 A
HO base load power
7.5 kW
11 kW
15 kW
HO base load input current
24.1 A
36.4 A
45.2 A
HO base load output current
16.5 A
25 A
31 A
Power loss with filter
349 W
435 W
503 W
Power loss without filter
344 W
429 W
493 W
Required cooling air flow
18 l/s
18 l/s
18 l/s
Weight with filter
4.7 kg
4.7 kg
4.7 kg
Weight without filter
4.4 kg
4.4 kg
4.4 kg
Table 10-8
Frame size D, 3 AC 380 V … 480 V, +10 %, -20 %
Article No. without filter
Article No. with filter
6SL3210-1KE24-4U . 1
6SL3210-1KE24-4A . 1
6SL3210-1KE26-0U . 1
6SL3210-1KE26-0A . 1
6SL3210-1KE27-0U . 1
6SL3210-1KE27-0A . 1
Rated/LO base load power
22 kW
30 kW
37 kW
Rated/LO base load input current
41 A
53 A
64 A
Rated/LO base load output current
43 A
58 A
68 A
HO base load power
18.5 kW
22 kW
30 kW
HO base load input current
39 A
44 A
61 A
HO base load output current
37 A
43 A
58 A
Power loss with filter
650 W
933 W
1.032 kW
Technical data
10.5 Technical data dependent on the power
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF