Parameter
Description
p0605
Mot_temp_mod 1/2 / sensor threshold and temperature value (factory setting: 145° C)
For monitoring the motor temperature using KTY84/Pt1000.
p0610
Motor overtemperature response (factory setting: 12)
Determines the inverter behavior when the motor temperature reaches the alarm
threshold p0604.
0:
Alarm (A07910), no fault
1:
Alarm A07910 and fault F07011
The inverter reduces the current limit.
2,
12:
Alarm A07910 and fault F07011
The inverter does not reduce the current limit.
p0640
Current limit [A]
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.