5.5.6
Standard Drive Control
Procedure for application class [1]: Standard Drive Control
Select the I/O configuration to preassign the inverter interfaces.
Factory setting of the interfaces (Page 88)
Default setting of the interfaces (Page 91)
Set the applicable motor standard and the inverter supply voltage.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has already been entered.
Set the most important parameters to suit your application.
Select the application:
● [0] Constant load: Typical applications include conveyor drives
● [1] Speed-dependent load: Typical applications include pumps and fans
Motor data identification (not all the following settings may be visible in Startdrive):
● [0]: No motor data identification
● [1]: Measure the motor data at standstill and with the motor rotating. The inverter switches
off the motor after the motor data identification has been completed.
● [2]: Recommended setting. Measure the motor data at standstill. The inverter switches off
the motor after the motor data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a mechanically limited traversing
range.
● [3]: Measure the motor data while the motor is rotating. The inverter switches off the motor
after the motor data identification has been completed.
● [11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
● [12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
You have completed quick commissioning.
Commissioning
5.5 Quick commissioning with a PC
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
143