Mounting the shield plates, FSAA … FSC
We recommend that you mount the shield plates provided. The shield plates make it simpler
to install the inverter in compliance with EMC regulations and to provide strength relief for the
connected cables.
01P
01P
)6$$01P
)6$)6&01P
Figure 4-10 Mounting the shield plates, FSAA … FSC
Mounting the shield plate and EMC connecting bracket, FSD … FSF
Procedure, FSD and FSE
Proceed as follows to mount the EMC connecting bracket and the shield plate:
1. If you are using an inverter with an integrated line filter, then mount the EMC connecting
bracket on the shield plate
①
.
On inverters without a filter, the EMC connecting bracket is not included in the scope of
supply of the inverter.
2. Then slide the shield module into the inverter, so that it is held in the inverter
②
by the
clamping spring. The shield module is located correctly if it can be easily withdrawn from
the inverter without any resistance.
3. After you have ensured that it is correctly located, fix the shield module using the four screws
③
.
1P
1P
You have mounted the EMC connecting bracket and the shield plate.
Installing
4.3 Installing the inverter
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
53