7
7.1 Phasor Measurement Unit (PMU)
59
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
The tables below give an overview of the data rates of the SIMEAS R-PMU depending on the
device configuration and the reporting rate with UDP and TCP communication via LAN.
Table 7-4
UDP transmission via LAN:
Data transfer rate depending on the configuration and reporting rate in kbit/s,
data format 16 bit integer
Configuration
Type
Reporting rate (Hz)
10
12
15
20
25
30
50
60
1 AC DAU
Positive-sequence system
5
6
7
9
12
14
23
28
1 AC DAU
Phasors
7
8
10
13
16
20
33
39
2 AC DAUs
Positive-sequence system
6
7
9
12
15
18
30
36
2 AC DAUs
Phasors
10
12
15
19
24
29
48
58
4 AC DAUs
Positive-sequence system
8
10
13
17
21
25
42
51
4 AC DAUs
Phasors
16
19
24
32
40
48
80
96
1 DDAU
Process values
5
6
8
11
13
16
27
32
2 DDAUs
Process values
7
9
11
14
18
22
36
43
1 BDAU
Binary values
4
5
6
8
11
13
21
25
2 AC DAUs
2 DDAUs
Positive-sequence system/
process values
11
13
16
22
27
33
55
66
2 AC DAUs
1 DDAU
1 BDAU
Phasors /
process values /
binary values
12
15
19
25
31
37
62
74
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...