12.7 Interfaces
147
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
A waiting time of 1000 ms has been preset.
Adjust the
INIT String
to suit your modem if necessary. It depends on the modem type that
is used. The default setting of the INIT string is:
ATQ0V1E0X0S0=1.
Enter the supplementary command for an AT command in the
Command Suffix
box. The
default setting of the supplementary command is:
^M
Enter the command for the end of the command line in the
Dialing Command
box. The
default setting of the command is
ATDT
for tone dialing and
ATDP
for impulse dialing.
If a modem is used, check the message texts for the following conditions:
Connect
,
Busy
,
No dial tone
and
Disconnect
and adjust them if necessary.
Note
If the data interface is used for the PMU, the baud rate is set to 115,200 bit/s (fixed). You can
only parameterize
Direct
and
HAYES Modem
. By activating the PMU, the baud rate will be set
to 115,200 bit/s automatically. Your previous baud rate parameterization will be lost.
Note
Set the same baud rate for the SIMEAS R-PMU and the PC or DAKON.
Note
Always enter an INIT string for dial-up modems.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...