12
12.2 Configuration
139
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Enter the
DAU Name
consisting of max. 8 characters that is to be used for recording the
events of the DAU.
Select the connection mode from the drop-down menu of the
Connection Mode [1/2]
field
to define how the measuring signals are recorded locally, e. g., STAR. You can set separate
recording types for the first and the second group of measured values. This specification is
not possible with BDAU and DDAU modules.
The following reference values are valid for connecting the measuring signals:
Star
Phase-to-ground
values
Delta
Phase-to-phase
values
Monophase/1-phase Phase
values
3-phase
Phase
currents
Check the appropriate
Calculate
checkbox if you want to measure only three phases in star
connection and have the starpoint voltage V
n
or the starpoint current I
n
calculated.
The result of the vector additions:
or
is then shown as the 4th and/or 8th channel.
For CDAU modules, select from the drop-down menu of the
Voltage Coupling
box a
VCDAU or a VDAU to establish a link between VCDAU voltage channels and CDAU current
channels for power calculation. If a CDAU is coupled to a voltage channel, both reference
groups of the CDAU are always set either for three-phase or for single-phase measurement
depending on the voltage channel connection (star/3-phase or 1-phase).
Activate the
180° phase shift for VCDAU, CDAU, VCDAU
checkbox if you have
connected the voltage and current channels according to the SIMEAS R V2/V3
connection diagrams.
Table 12-1
Settings of voltage and current groups for a VCDAU
Voltage group
Current group
Power calculation
Star
3 phase
yes
Delta
3 phase
yes
Monophase
1 phase
yes
Star
1 phase
no
Delta
1 phase
no
Monophase
3 phase
no
Vn
1
3
---
V
L1
V
L2
V
L3
]
+
+
[
=
In
I
L1
I
L2
I
L3
+
+
[
]
–
=
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...