3 System Messages
281
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
291
2
SYSTEM
Restart cause: File system cannot be
initialized
Flash disk fault; Hotline
292
2
SYSTEM
Restart cause: Log recorder cannot be
initialized. Time stamp:
Flash disk fault; Hotline
293
2
SYSTEM
Restart cause: Folder tree structure cannot
be initialized. Time stamp:
Flash disk fault; Hotline
294
2
SYSTEM
Restart cause: Battery fault.
Time stamp:
Replace battery pack
295
2
SYSTEM
Restart cause: Fault in log recorder queue.
Time stamp:
Hotline
296
2
SYSTEM
Restart cause: Log recorder cannot be
opened. Time stamp:
Hotline
297
2
SYSTEM
Restart cause: Invalid log recorder format.
Time stamp:
Hotline
298
2
SYSTEM
Critical system fault: Task suspended.
Task no.:
Hotline
299
2
SYSTEM
Critical system fault: Recorder task
suspended. Task no.:
Hotline
300
0
SYSTEM
Self-monitoring: DAU fault
DAU hardware/software fault; Hotline
384
0
BOOT
Mismatch fault: DAU found but not
configured
All plugged in DAUs must be
parameterized. DAUs not needed can be
deactivated.
386
1
BOOT
Fault: DAU configured but not plugged in
Parameterized DAUs must be plugged in
387
0
BOOT
Fault booting the DAU
Hotline
388
1
BOOT
Mismatch fault: Incorrect DAU configured
Wrong DAU type parameterized
389
0
BOOT
Fault configuring the DAU
Several possible reasons: DAU and CPU
software version do not match, firmware
update recommended; DAU hardware error;
contact hotline if necessary
390
0
BOOT
Fault setting the DAU time
Hotline
393
0
BOOT
Fault starting DAU
Hotline, DAU hardware error
395
2
BOOT
DAU type slot 1
-
396
2
BOOT
DAU type slot 2
-
397
2
BOOT
DAU type slot 3
-
398
2
BOOT
DAU type slot 4
-
399
2
BOOT
Device booting with firmware version:
-
400
0
BOOT
Fault booting the communication processor.
Internal fault number:
Hotline, CPU or DAU hardware fault
401
1
BOOT
DAU deactivated
-
402
1
BOOT
Initialization finished
Possibly an error message after an
upgrade; otherwise hotline
(consider additional texts)
403
1
BOOT
DAU calibration frequency 16.66 Hz, type
not supported
SIMEAS R-PMU supports 50 Hz and 60 Hz
DAU types only.
Nevertheless, the device is ready for work
generating wrong measured values.
404
1
BOOT
Wrong DAU calibration frequency of 50 Hz
for 60 Hz system
Only 60 Hz DAU types are allowed for
60 Hz nominal frequency.
Nevertheless, the device is ready for work
generating wrong measured values.
405
1
BOOT
Wrong DAU calibration frequency of 60 Hz
for 50 Hz system
Only 50 Hz DAU types are allowed for
50 Hz nominal frequency.
Nevertheless, the device is ready for work
generating wrong measured values.
406
1
BOOT
Unknown DAU calibration frequency
Hotline, DAU hardware fault
Log No.
Type
Class
Description
Comment
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...