16
16.1 Technical Data of the SIMEAS R-PMU
253
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Surge
IEC 61000-4-5
extended as per customer requirements
Power supply, control and
communications lines
Common mode 4 kV,
Differential mode 2 kV (extended 4 kV)
Damped oscillation
IEC 61000-4-18; EN 61000-4-18
Damped oscillation
Test level 3,
Common mode 2.5 kV
Differential mode 1 kV
Repetition rate 100 kHz and 1 MHz
Voltage dips and
short interruptions
IEC 61000-4-11; EN 61000-4-11
IEC 60255-11
Short interruption 100 % to 0 % for 50 ms
Short interruption 100 % to 50 % for 100 ms
Voltage fluctuations
IEC 61000-4-11; EN 61000-4-11
AC/DC power supply unit
to 80 %, 120 % permanently,
to 40 %, dynamic 2 s, operation 2 s
to 0 %, dynamic 2 s, operation 1 s
Voltage interruptions
IEC 61000-4-11; EN 61000-4-11
AC power supply unit
to 0 % for 5 s with 50 Hz / 60 Hz
±
5 %
switch OFF and automatic restart
Voltage dips
IEC 61000-4-11; EN 61000-4-11
AC power supply unit
to 0 % for 10 ms
to 40 % for 100 ms
to 70 % for 200 ms with 50 Hz / 60 Hz
±
5 %
Function not affected
Interference emission
IEC/EN 61000-6-4
Interference field strength
EN55011/CISPR11
Class A
Radio interference voltage
EN55011/CISPR11
Class A
Harmonics
AC supply voltage
IEC 61000-3-2; EN 61000-3-2
AC power supply unit
Class A
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...